Freeze and Hot Tap Case History #28

Freeze and Hot Tap Case History #28

Freeze and Hot Tap Case History #28 Objective: Mill out gate to 3 1/8 diameter on top master valve that is seized closed and freewheeling to accommodate wireline tools and installation of back pressure valve in tubing hanger. Bottom master Valve previously milled out....
Freeze and Hot Tap Case History #27

Freeze and Hot Tap Case History #27

Freeze and Hot Tap Case History #27 Objective: Hot tap and mill out a damaged gate valve 90% closed and freewheeling. Well Information: 4,200kpa sweet gas well on an offshore platform with damaged gate valve not allowing access into tubing. Top gate valve functioning....
Freeze and Hot Tap Case History #27

Freeze and Hot Tap Case History #26

Freeze and Hot Tap Case History #26 Objective: Hot tap and Freeze tubing to replace damaged master valve to gain entrance into tubing. Well Information: 12.4MPa sour gas well shut in for several years, master valve seized. Procedure: Heat wellhead, expose surface...
Freeze and Hot Tap Case History #27

Freeze and Hot Tap Case History #25

Freeze and Hot Tap Case History #25 Objective: Freeze well to install another 7 1/16” gate valve. Well Information: 30 mPa BHP. Wire line tools were hydrated in the hole approximately 150 meters down and braided line was across existing gate valve. Wireline lubricator...
Freeze and Hot Tap Case History #27

Freeze and Hot Tap Case History #24

Freeze and Hot Tap Case History #24 Objective: Freeze casing to install primary seal on intermediate casing. Well Information: 51 mPa Bottom hole pressure. Failed cement job was allowing pressure to surface on intermediate casing side where there was no primary seal...